Smart-UPS On-Line

SURT20KRMXLT

Availability:

Quick Overview

APC Smart-UPS RT 20kVA RM 208V

Includes: CD with software, Rack Mounting support rails, Smart UPS signalling RS-232 cable, User Manual, Web/SNMP Management Card

Standard Lead Time: Usually in Stock

SURT20KRMXLT

More Views

  • SURT20KRMXLT

Details

Output

Output Power Capacity
16 kW / 20 kVA
Max Configurable Power
16 kW / 20 kVA
Nominal Output Voltage
208V
Output Voltage Note
Configurable for 208 or 240 nominal output voltage
Efficiency at Full Load
94%
Output Voltage Distortion
Less than 5%
Output Frequency (sync to mains)
50/60 Hz +/- 3 Hz user adjustable +/- 0.1
Crest Factor
3 : 1
Waveform Type
Sine wave
Output Connections
(1) Hard Wire 3-wire (2PH + G)  
(4) NEMA L6-20R
(2) NEMA L6-30R
Overload Operation
60 seconds @ 125% and 30 seconds @ 150%
Efficiency at Half Load
94%
Bypass
Built-in Static Bypass,Internal Bypass (Automatic and Manual),Optional External Bypass

Input

Nominal Input Voltage
208V
Input Frequency
40 - 70 Hz (auto sensing)
Input Connections
Hard Wire 3-wire (2PH + G)  
Input voltage range for main operations
160 - 280V
Other Input Voltages
240
Maximum Input Current
114A
Input Breaker Capacity
125.0  A
Input Total Harmonic Distortion
Less than 5% for full load

Batteries & Runtime

Battery Type
Maintenance-free sealed Lead-Acid battery with suspended electrolyte : leakproof
Included Battery Modules
4
Typical recharge time
2.50 hour(s)
Replacement Battery
RBC™ Quantity
4
Nominal Battery Voltage
+/-192 V (split battery referenced to neutral)
End of Discharge Battery Voltage
+/-154 V
Efficiency in Battery Operation
93%
Extended Run Options
APC Smart-UPS RT 20kVA RM 208V

Communications & Management

Interface Port(s)
DB-9 RS-232,RJ-45 10/100 Base-T,Smart-Slot
Pre-Installed SmartSlot™ Cards
Control panel
Multi-function LCD status and control console
Audible Alarm
Audible and visible alarms : configurable delays
Emergency Power Off (EPO)
Yes

Surge Protection and Filtering

Filtering
Full time multi-pole noise filtering : 0.3% IEEE surge let-through : zero clamping response time : meets UL 1449

Physical

Maximum Height
20.98 inches (533 mm)
Maximum Width
17.00 inches (432 mm)
Maximum Depth
30.43 inches (773 mm)
Rack Height
12U
Net Weight
545.00 lbs. (247.73 kg)
Shipping Weight
691.40 lbs. (314.27 kg)
Shipping Height
38.98 inches (990 mm)
Shipping Width
24.02 inches (610 mm)
Shipping Depth
39.49 inches (1003 mm)
Color
Black
Units per Pallet
1.00

Environmental

Operating Environment
32 - 104 °F (0 - 40 °C)
Operating Relative Humidity
0 - 95%
Operating Elevation
0-10000 feet (0-3000 meters)
Storage Temperature
5 - 113 °F (-15 - 45 °C)
Storage Relative Humidity
0 - 95%
Storage Elevation
0-50000 feet (0-15000 meters)
Audible noise at 1 meter from surface of unit
59.00 dBA
Online Thermal Dissipation
4320.00 BTU/hr

Conformance

Regulatory Approvals
UL 1778
Standard Warranty
2 years repair or replace