Symmetra

SYPM10KF2

Availability:

Quick Overview

Symmetra PX 10kW Power Module, 208V, High Efficiency



APC Symmetra Power Module,10 kW /10 kVA,Input 208V, 208V 3PH /Output 208V, 208V 3PH, Extended runtime model

SYPM10KF2

More Views

  • SYPM10KF2

Details

 

Output

Output Power Capacity
10 kW / 10 kVA
Max Configurable Power
10 kW / 10 kVA
Nominal Output Voltage
208V, 208V 3PH
Efficiency at Full Load
94.7%
Output Voltage Distortion
Less than 5% at full load
Output Frequency (sync to mains)
57 - 63 Hz for 60 Hz nominal
Crest Factor
Unlimited
Topology
Double Conversion Online
Waveform Type
Sine wave

Input

Nominal Input Voltage
208V, 208V 3PH
Input Frequency
60 Hz +/- 3 Hz
Input voltage range for main operations
177 - 239 (208V)V

Communications & Management

Audible Alarm
Alarm when on battery : distinctive low battery alarm : configurable delays
Emergency Power Off (EPO)
--

Physical

Maximum Height
5.20 inches (132 mm)
Maximum Width
19.02 inches (483 mm)
Maximum Depth
27.56 inches (700 mm)
Net Weight
55.10 lbs. (25.05 kg)
Shipping Weight
61.70 lbs. (28.05 kg)
Shipping Height
8.86 inches (225 mm)
Shipping Width
23.43 inches (595 mm)
Shipping Depth
31.30 inches (795 mm)
Color
Black

Environmental

Operating Environment
32 - 104 °F (0 - 40 °C)
Operating Relative Humidity
0 - 95%
Operating Elevation
0-3333 feet (0-999.9 meters)
Storage Temperature
5 - 104 °F (-15 - 40 °C)
Storage Relative Humidity
0 - 95%
Storage Elevation
0-15000 feet (0-4500 meters)
Audible noise at 1 meter from surface of unit
64.00 dBA
Online Thermal Dissipation
2970.00 BTU/hr

Conformance

Regulatory Approvals
cUL Listed, FCC Part 15 Class A, ISO 14001, ISO 9001, UL 60950, UL Listed
Standard Warranty
1 year repair or replace

Sustainable Offer Status

RoHS
Compliant
REACH
REACH: Contains No SVHCs