Switched Rack PDU
AP8981
Availability:
Quick Overview
Rack PDU 2G, Switched, ZeroU, 11kW, 230V, (21) C13 & (3) C19
Includes: Installation guide, Rack Mounting brackets, Safety guide, Sample locking IEC power cord, Serial configuration cable
Standard Lead Time: Usually in Stock
Details
Output
Nominal Output Voltage
208V,230V
Maximum Total Current Draw per Phase
16A
Output Connections
(21) IEC 320 C13 | ![]() |
(3) IEC 320 C19 | ![]() |
Overload Protection
No
Input
Nominal Input Voltage
400V 3PH
Input Frequency
50/60 Hz
Regulatory Derated Input Current (North America)
16A
Input Connections
IEC 309 16A 3P+N+PE | |
IEC 309 20A 3P+N+E |
Cord Length
6 feet (1.83 meters)
Number of Power Cords
1
Maximum Line Current per phase
20A
Maximum Input Current per phase
20A
Physical
Net Weight
15.40 lbs. (7.00 kg)
Maximum Height
70.50 inches (1791 mm)
Maximum Width
2.20 inches (56 mm)
Maximum Depth
1.82 inches (46 mm)
Shipping Weight
19.70 lbs. (8.95 kg)
Shipping Height
78.80 inches (2002 mm)
Shipping Width
6.50 inches (165 mm)
Shipping Depth
4.50 inches (114 mm)
Color
Black
Environmental
Operating Environment
23 - 113 °F (-5 - 45 °C)
Operating Relative Humidity
5 - 95%
Operating Elevation
0-10000 feet (0-3000 meters)
Storage Temperature
-13 - 149 °F (-25 - 65 °C)
Storage Relative Humidity
5 - 95%
Storage Elevation
0-50000 feet (0-15000 meters)
Conformance
Regulatory Approvals
cUL Listed,EN 55022 Class A,EN 55024,EN 61000-3-2,EN 61000-3-3,FCC Part 15 Class A,ICES-003,UL Listed,VDE
Standard Warranty
2 years repair or replace
Environmental Compliance
RoHS,REACH: Contains No SVHCs,Contains Lithium Battery